OnSumo Tools

Voltage Drop Calculator

Calculate voltage drop in volts and percent for any AWG, length, and conduit type, with a full gauge comparison against NEC 3% and 5% guidance.

100% client-side. Inputs stay in your browser (ons-voltage-drop-inputs).

Inputs

Results

Fail (>5%)Smallest AWG at or under 3% in table: 8 AWG

Voltage drop

7.72 V (6.43%)

Receiving voltage

112.28 V

Selected wire

12 AWG

AWGVD %VD (V)Status
1410.23%12.28Fail
12(selected)6.43%7.72Fail
104.03%4.84Marginal
82.55%3.06Pass
61.64%1.96Pass
41.03%1.23Pass
20.65%0.78Pass
1/00.41%0.49Pass
2/00.32%0.39Pass
3/00.26%0.31Pass
4/00.20%0.24Pass

Based on NEC 2023, Chapter 9 Table 9 (AC resistance) with Table 8 baseline. Verified 2026-05-25.

Resistance comes from NEC Chapter 9 Table 9 style values: Table 8 ohms per thousand feet for copper or aluminum, adjusted for steel EMT, PVC, or aluminum raceway. Single-phase drop is 2 × one-way length × amps × ohms per foot. Three-phase uses √3 × length × amps × R. We flag 3% as a pass (branch recommendation) and up to 5% as marginal (feeder plus branch guidance). The comparison table runs the same math for every common AWG so you can see the smallest size that stays under 3%.

Consult a licensed electrician before installation. Local codes may be more stringent than NEC recommendations.

How this tool works

Resistance comes from NEC Chapter 9 Table 9 style values: Table 8 ohms per thousand feet for copper or aluminum, adjusted for steel EMT, PVC, or aluminum raceway. Single-phase drop is 2 × one-way length × amps × ohms per foot. Three-phase uses √3 × length × amps × R. We flag 3% as a pass (branch recommendation) and up to 5% as marginal (feeder plus branch guidance). The comparison table runs the same math for every common AWG so you can see the smallest size that stays under 3%.

Worked example

A 20 amp, 120 volt copper branch on 12 AWG PVC conduit with a 100-foot one-way run drops about 7.7 volts (6.4%). That is above the 3% branch guideline, so the table points you to 8 AWG (about 2.6% on the same run). Shorten the run to 40 feet and 12 AWG lands near 2.6% while 14 AWG is still over 4%.

Frequently asked questions

  • What is the NEC voltage drop limit?

    The National Electrical Code recommends (but does not mandate) a maximum 3% voltage drop on branch circuits and 5% total from the service panel to the furthest outlet, including both feeder and branch circuit drop. NEC Article 210.19(A) and 215.2(A) state these as recommendations in informational notes, not enforceable requirements. However, many jurisdictions enforce the 3% limit, and it is industry standard practice. Sensitive electronics, motors, and medical equipment benefit from stricter limits of 1-2% because voltage drop reduces both efficiency and equipment lifespan.

  • Why does voltage drop matter?

    Voltage drop reduces the effective voltage reaching a load, which affects performance and efficiency in proportion to the square of the voltage for resistive loads. A motor receiving 108V on a 120V circuit (10% drop) draws more current to maintain torque, increasing heat buildup and accelerating winding insulation degradation. LED drivers and variable-frequency drives are sensitive to input voltage levels. Long runs to outbuildings, barns, pumps, or shop equipment are common sources of excessive voltage drop that cause nuisance tripping, poor motor performance, and early equipment failure.

  • Does conduit material affect voltage drop?

    Conduit material has a negligible effect on voltage drop itself, which is determined by conductor resistance, current, and length. However, steel conduit (EMT, rigid) creates a slight inductive effect for AC circuits that marginally increases impedance on long runs -- typically less than 1-2% additional impedance compared to PVC conduit. The more significant conduit-related factor is temperature: conductors in tightly packed metallic conduit may run hotter due to reduced heat dissipation, which increases conductor resistance (copper resistance rises about 0.4% per degree C) and worsens voltage drop on loaded circuits.

  • What are the most effective ways to reduce voltage drop?

    In order of effectiveness: (1) increase conductor size -- going from 12 AWG to 10 AWG cuts resistance by 37%; (2) shorten the run by relocating the panel or subpanel closer to the load; (3) increase circuit voltage from 120V to 240V -- this cuts current in half for the same wattage and reduces drop by 75%; (4) use parallel conductors for very high-current loads. Increasing conductor size is the most common field solution. Going up two AWG sizes (e.g., 12 to 8 AWG) reduces resistance by approximately 60%.

  • Why does using 240V instead of 120V cut voltage drop so dramatically?

    Power equals voltage times current (P = V x I). To deliver the same wattage at twice the voltage, you need half the current. Voltage drop equals current times resistance (V = I x R). Half the current produces half the voltage drop in absolute volts, and as a percentage of the higher supply voltage the improvement is even greater. A 10-amp load on 120V that produces 3V of drop (2.5%) would only draw 5 amps on 240V, producing 1.5V of drop -- just 0.625% of 240V. This is why large appliances (dryers, ranges, EV chargers, well pumps) run on 240V circuits.

  • How does ambient temperature affect wire resistance and voltage drop?

    Copper resistance increases linearly with temperature at approximately 0.393% per degree Celsius. A conductor operating at 75 degrees C has about 20% higher resistance than the same conductor at 20 degrees C, directly increasing voltage drop by 20% for the same current. NEC ampacity tables assume 60, 75, or 90 degree C conductor temperature ratings depending on insulation type. Conduit runs in hot attics or in direct sun can see ambient temperatures of 50 degrees C or higher, which significantly derates both ampacity and effective resistance. Always derate voltage drop calculations for high-temperature environments by using the resistance at expected operating temperature.

Related tools